Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 12
Carefully seat the heat sink over the processor, aligning the four screws with the holes in the 11 .
logic board.
Tighten the four captive Phillips mounting screws for the heat sink in the order indicated 12.
below. Do not over-tighten the screws. If you have a torque driver, tighten the screws to 8
inch-pounds; otherwise, try to tighten the screws with equal pressure.
Replacing the Airow Duct
Lower the airow duct into position on the logic board. 1.
Note: When installing the airow duct, be sure to route both the front panel board cable and
the backplane-to-logic board I/O cable inside the channel under the left side of the duct.